7.3.9.9. CO
2
consumption and generation emissions.
Table 86: Modbus memory map: CO
2
consumption and generation emissions.
CO
2
emissions
Configuration variable
(11)
Address Valid data margin
Default
value
Tariff 1 consumption emissions ratio 2724 0 - 1.9999 0
Tariff 2 consumption emissions ratio 2725 0 - 1.9999 0
Tariff 1 generation emissions ratio 2728 0 - 1.9999 0
Tariff 2 generation emissions ratio 2729 0 - 1.9999 0
(11)
They have 1 decimal place.
7.3.9.10. Cost of energy consumption and generation.
Table 87: Modbus memory map: Cost of energy consumption and generation.
Cost per kWh
Configuration variable
(12)
Address Valid data margin
Default
value
Cost per kWh of tariff 1 consumption 272C 0 - 1.9999 0
Cost per kWh of tariff 2 consumption 272D 0 - 1.9999 0
Cost per kWh of tariff 1 generation 2730 0 - 1.9999 0
Cost per kWh of tariff 2 generation 2731 0 - 1.9999 0
(12)
They have 1 decimal place.
7.3.9.11. Programming Digital Output T1
Note: The CVM-E3-MINI-xxx-WiEth models do not have a Digital Output, so the alarm only triggers
the activation of the ALARM / ENERGY PULSES LED.
Table 88: Modbus memory map: Programming Digital Output T1 (Alarm)
Programming Digital Output : Alarm
Configuration variable Address Valid data margin Default value
Maximum value 2AF8-2AF9 depending on the variable 0
Minimum value 2AFA-2AFB depending on the variable 0
Variable code 2AFC Table 38 and Table 39 0
Connection delay 2AFD 0 - 9999 seconds 0
Hysteresis 2AFE 0 - 99 % 0
Latch 2AFF
0 : No
1: Yes
0
Latch time
(13)
2B02 0 - 600 seconds 0
Disconnection delay 2B00 0 - 9999 seconds 0
Contacts status 2B01
0 : Normally open
1: Normally closed
0
(18)
The latch time is the time in seconds when the alarm will be latched. After this time, if the alarm condition has cleared,
the disconnection delay is activated If a 0 is programmed, the alarm remains latched and can only be unlatched manually.
Table 89: Modbus memory map: Programming Digital Output T1 (pulses output)
Programming Digital Output : Pulses output
Configuration variable Address Valid data margin Default value
Kilowatts per impulse 2B20-2B21 0.001 - 999.99 kWh 1.00 kWh
Variable code 2AFC Table 40 0
Pulse width 2B22 30 - 500 ms 100 ms
100
CVM-E3-MINI
Instruction Manual