Table 66: Modbus memory Map 2: Energy variables
Map 2
Parameter Symbol Tariff 1 Tariff 2 Total Units
Consumed active energy III (kWh) kWh III 105E-105F 1088-1089 10DC-10DD kWh
Consumed active energy III (Wh) kWh III 1060-1061 108A-108B 10DE-10DF Wh
Consumed inductive reactive energy III
(kvarhL)
kvarhL III 1062-1063 108C-108D 10E0-10E1 kvarh
Consumed inductive reactive energy III
(varhL)
kvarhL III
1064-1065 108E-108F 10E2-10E3 varh
Consumed capacitive reactive energy III
(kvarhC)
kvarhC III
1066-1067 1090-1091 10E4-10E5 kvarh
Consumed capacitive reactive energy III
(varhC)
kvarhC III
1068-1069 1092-1093 10E6-10E7 varh
Consumed apparent energy III (kVAh) kVAh III 106A-106B 1094-1095 10E8-10E9 kVAh
Consumed apparent energy III (VAh) kVAh III 106C-106D 1096-1097 10EA-10EB VAh
Consumed CO
2
emissions KgCO
2
106E-106F 1098-1099 10EC-10ED x10
Consumption cost $ 1070-1071 109A-109B 10EE-10EF x10
Generated active energy III (kWh) kWh III 1072-1073 109C-109D 10F0-10F1 kWh
Generated active energy III (Wh) kWh III 1074-1075 109E-109F 10F2-10F3 Wh
Generated inductive reactive energy III
(kvarhL)
kvarhL III
1076-1077 10A0-10A1 10F4-10F5 kvarh
Generated inductive reactive energy III
(varhL)
kvarhL III
1078-1079 10A2-10A3 10F6-10F7 varh
Generated capacitive reactive energy III
(kvarhC)
kvarhC III
107A-107B 10A4-10A5 10F8-10F9 kvarh
Generated capacitive reactive energy III
(varhC)
kvarhC III
107C-107D 10A6-10A7 10FA-10FB varh
Generated apparent energy III (kVAh) kVAh III 107E-107F 10A8-10A9 10FC-10FD kVAh
Generated apparent energy III (VAh) kVAh III 1080-1081 10AA-10AB 10FE-10EF VAh
Generated CO
2
emissions KgCO
2
1082-1083 10AC-10AD 1100-1101 x10
Generation Cost $ 1084-1085 10AE-10AF 1102-1103 x10
Hours per tariff Hours 1086-1087 10B0-10B1 1104-1105 seg
Table 67: Modbus memory Map 1 and Map 2 (energy variables per phase).
Map 1 and Map 2
Parameter Symbol L1 L2 L3 Units
Consumed active energy (kWh) T1 kWh 1400-1401 1460-1461 14C0-14C1 kWh
Consumed active energy (Wh) T1 kWh 1402-1403 1462-1463 14C2-14C3 Wh
Consumed inductive reactive energy T1
(kvarhL)
kvarhL 1404-1405 1464-1465 14C4-14C5 kvarh
Consumed inductive reactive energy T1 (var-
hL)
kvarhL
1406-1407 1466-1467 14C6-14C7 varh
Generated active energy T1 (kWh) kWh 1410-1411 1470-1471 14D0-14D1 kWh
Generated active energy T1 (Wh) kWh 1412-1413 1472-1473 14D2-14D3 Wh
Generated inductive reactive energy T1
(kvarhL)
kvarhL
1414-1415 1474-1475 14D4-14D5 kvarh
Generated inductive reactive energy T1 (var-
hL)
kvarhL
1416-1417 1476-1477 14D6-14D7 varh
Consumed active energy (kWh) T2 kWh 1420-1421 1480-1481 14E0-14E1 kWh
Consumed active energy (Wh) T2 kWh 1422-1423 1482-1483 14E2-14E3 Wh