4-12
Cisco SCE8000 GBE Installation and Configuration Guide
OL-19897-02
Chapter 4 Installing the Cisco SCE8000 GBE Chassis
Preparing for Installation
Table 4-5 lists the Cisco SCE 8000 GBE DC power supply specification.
Note The DC supplies each have the provision for a dual connection to the power source in order to permit
high-power operation without exceeding current ratings. For the SCE 8000, it is not necessary to connect
both of these inputs to DC power sources; it is sufficient to connect only the '1' connections.
Table 4-5 Cisco SCE 8000 GBE DC Power Supply Specification
Specification Acceptable Range
PWR-2700-DC/4 minimum
capability
1350W output (1750W input)
DC-input power consumption
Single SCE8000-SCM-E module:
1000 W / 3450 BTUs
Dual SCE8000-SCM-E modules:
1600 W / 5464 BTUs
DC-input voltage rating -48 VDC to -40VDC
(operating range: -40.5 VDC to -72 VDC)
DC-input current rating 45 A maximum at 120 VAC
DC-input cable Accepts 2-14 AWG copper conductors. Actual size of the wire
needed is determined by the installer or local electrician.
Terminal block material rated at 150°C.
DC-input circuit breaker For multiple DC input power supplies, each DC input must be
protected by a dedicated two-pole circuit breaker or a fuse.
The circuit breaker or the fuse must be sized according to the
power supply input power rating and any local or national
electrical code requirements.