Table 58: Query
Field name Example (hex)
Follower address 01
Function 06
Register address HI 03 (register address 999)
Register address LO E7 (register address 999)
Preset data HI 00
Preset data LO 01
Error check (CRC)
Response
The normal response is an echo of the query, returned after the register contents have been passed.
Table 59: Response
Field name Example (hex)
Follower address 01
Function 06
Register address HI 03
Register address LO E7
Preset data HI 00
Preset data LO 01
Error check (CRC)
9.10.7 Preset Multiple Registers (10 hex)
Description
This function presets values into a sequence of holding registers.
Query
The query telegram specifies the register references to be preset. Register addresses start at 0, that is, register 1 is addressed as 0.
Example of a request to preset 2 registers (set parameter 1-24 Motor Current to 738 (7.38 A)):
Table 60: Query
Field name Example (hex)
Follower address 01
Function 10
Starting address HI 04
Starting address LO 07
112 | Danfoss A/S © 2024.01 AJ435824192086en-000101 / 130R1295
Design Guide | VLAutomationDrive FC 360

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals