Bit 07=0: There are no warnings.
Bit 07=1: A warning has occurred.
Bit 08, Speed reference/speed=reference
Bit 08=0: The motor runs, but the present speed is different from the preset speed reference. It might happen when the speed ramps up/
down during start/stop.
Bit 08=1: The motor speed matches the preset speed reference.
Bit 09, Local operation/bus control
Bit 09=0: [Off/Reset] is activated on the control unit or [2] Local in parameter 3-13 Reference Site is selected. It is not possible to control
the drive via serial communication.
Bit 09=1: It is possible to control the drive via the fieldbus/serial communication.
Bit 10, Out of frequency limit
Bit 10=0: The output frequency has reached the value in parameter 4-12 Motor Speed Low Limit [Hz] or parameter 4-14 Motor Speed
High Limit [Hz].
Bit 10=1: The output frequency is within the defined limits.
Bit 11, No operation/in operation
Bit 11=0: The motor is not running.
Bit 11=1: The drive has a start signal without coast.
Bit 12, Drive OK/stopped, auto start
Bit 12=0: There is no temporary overtemperature on the drive.
Bit 12=1: The drive stops because of overtemperature, but the unit does not trip and resumes operation once the overtemperature
normalizes.
Bit 13, Voltage OK/limit exceeded
Bit 13=0: There are no voltage warnings.
Bit 13=1: The DC voltage in the drives DC link is too low or too high.
Bit 14, Torque OK/limit exceeded
Bit 14=0: The motor current is lower than the current limit selected in parameter 4-18 Current Limit.
Bit 14=1: The current limit in parameter 4-18 Current Limit is exceeded.
Bit 15, Timer OK/limit exceeded
Bit 15=0: The timers for motor thermal protection and thermal protection are not exceeded 100%.
Bit 15=1: 1 of the timers exceeds 100%.
9.11.3 Bus Speed Reference Value
Speed reference value is transmitted to the drive in a relative value in %. The value is transmitted in the form of a 16-bit word. The integer
value 16384 (4000 hex) corresponds to 100%. Negative figures are formatted using 2’s complement. The actual output frequency (MAV)
is scaled in the same way as the bus reference.
118 | Danfoss A/S © 2024.01 AJ435824192086en-000101 / 130R1295
Design Guide | VLAutomationDrive FC 360

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals