During low mains voltage or a mains dropout, the drive continues until the DC-link voltage drops below the minimum stop level, which
corresponds typically to 15% below the lowest rated supply voltage of the drive. Power-up and full torque cannot be expected at mains
voltage lower than 10% below the lowest rated supply voltage of the drive.
The drive is suitable for use on a circuit capable of delivering up to 100 kA short-circuit current rating (SCCR) at 480/600 V.
5.3 Motor Output (U, V, W)
Output voltage 0–100% of supply voltage
Output frequency in U/f mode (for AM motor) 0–500 Hz
Output frequency in VVC+ mode (for AM motor) 0–200 Hz
Output frequency in VVC+ mode (for PM motor) 0–400 Hz
Switching on output Unlimited
Ramp times 0.01–3600 s
5.4 Torque Characteristics
Starting torque (constant torque) Maximum 150% for 60 s
1)(1)2)(2)
Overload torque (constant torque) Maximum 150% for 60 s
(1)(2)
1) Percentage relates to the nominal current of the drive.
2) Once every 10 minutes.
5.5 Ambient Conditions
J8/J9 enclosure size IP20/Chassis
Vibration test (standard/ruggedized) 0.7 g
Relative humidity 5%–95% (IEC 721-3-3; Class 3K3 (non-condensing) during opera-
tion)
Aggressive environment (IEC 60068-2-43) H
2
S test Class Kd
Aggressive gases (IEC 60721-3-3) Class 3C3
Test method according to IEC 60068-2-43 H
2
S (10 days)
Ambient temperature (at SFAVM switching mode)
- with derating Maximum 55 °C (131 °F)
1)(1)
- with full output power of typical EFF2 motors (up to 90% output
current)
Maximum 50 °C (122 °F)
(1)
- at full continuous FC output current Maximum 45 °C (113 °F)
(1)
Minimum ambient temperature during full-scale operation -15 °C (5 °F)
Minimum ambient temperature at reduced performance -20 °C (-4 °F)
Temperature during storage/transport -25 to +65/70 °C (13 to 149/158 °F)
28 | Danfoss A/S © 2024.01 AJ435824192086en-000101 / 130R1295
Design Guide | VLT® AutomationDrive FC 360