During low mains voltage or a mains dropout, the drive continues until the DC-link voltage drops below the minimum stop level, which
corresponds typically to 15% below the lowest rated supply voltage of the drive. Power-up and full torque cannot be expected at mains
voltage lower than 10% below the lowest rated supply voltage of the drive.
The drive is suitable for use on a circuit capable of delivering up to 100 kA short-circuit current rating (SCCR) at 480/600 V.
5.3 Motor Output (U, V, W)
Output voltage 0–100% of supply voltage
Output frequency in U/f mode (for AM motor) 0–500 Hz
Output frequency in VVC+ mode (for AM motor) 0–200 Hz
Output frequency in VVC+ mode (for PM motor) 0–400 Hz
Switching on output Unlimited
Ramp times 0.01–3600 s
5.4 Torque Characteristics
Starting torque (constant torque) Maximum 150% for 60 s
1)(1)2)(2)
Overload torque (constant torque) Maximum 150% for 60 s
(1)(2)
1) Percentage relates to the nominal current of the drive.
2) Once every 10 minutes.
5.5 Ambient Conditions
J8/J9 enclosure size IP20/Chassis
Vibration test (standard/ruggedized) 0.7 g
Relative humidity 5%–95% (IEC 721-3-3; Class 3K3 (non-condensing) during opera-
tion)
Aggressive environment (IEC 60068-2-43) H
2
S test Class Kd
Aggressive gases (IEC 60721-3-3) Class 3C3
Test method according to IEC 60068-2-43 H
2
S (10 days)
Ambient temperature (at SFAVM switching mode)
- with derating Maximum 55 °C (131 °F)
1)(1)
- with full output power of typical EFF2 motors (up to 90% output
current)
Maximum 50 °C (122 °F)
(1)
- at full continuous FC output current Maximum 45 °C (113 °F)
(1)
Minimum ambient temperature during full-scale operation -15 °C (5 °F)
Minimum ambient temperature at reduced performance -20 °C (-4 °F)
Temperature during storage/transport -25 to +65/70 °C (13 to 149/158 °F)
28 | Danfoss A/S © 2024.01 AJ435824192086en-000101 / 130R1295
Design Guide | VLAutomationDrive FC 360

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals