5.8.3 MULTISET
NOTE: These settings are not stored in the module configuration. They are stored in a different
memory area and not transferred with the configuration. The Clone Module feature transfers both the
configuration AND the settings of the Multiset, Governor/AVR interface and the Sync page.
KVAr control The amount of reactive power that the set will produce when used in
‘load level control’ mode, when Reactive Load Control Mode is set to
Load Level Control
Pf control The power factor that the set will maintain when used in ‘load level
control’ mode, when Reactive Load Control Mode is set to Load
Level Control)
NOTE: At low load levels, it may not be possible to
maintain the power factor.
Each controller connected to the MSC link
must have a unique ID.
If all the controllers are powered up “one at a
time”, this DeviceID is automatically set.
Powering them up together may result in “ID
alarm”. Manually setting the DeviceID here will
Set Priority used when
the load demand
scheme is in operation
Enable or disable the module’s
diagnostic Commissioning Screens.
Load levels used when ‘base load’ / ‘fixed export’
mode is in operation (see below for details)
The number of modules currently connected to
the MSC link