4.7.5 GENERATOR POWER
The Power page is subdivided into smaller sections.
Select the required section with the mouse.
4.7.5.1 OVERLOAD PROTECTION
Overload protection is a subpage of the Generator Power page.
Overload Protection
= Overload Protection function is disabled.
= The module will monitor the kW load level and provide an alarm function if the
level exceeds the Trip setting for the configured amount of time in the Delay setting.
Action
Electrical Trip: The generator is taken off load and the set stopped after the Cooling
timer. Any output or LCD display set to kW Overload Protection is energised.
Indication: No alarm is generated; however any output or LCD display set to kW
Overload Protection is energised. The kW load must fall below the Return level in
order to cancel the output source.
Shutdown: The generator is taken off load and the set stopped immediately.
Warning: An alarm is generated but the set continues to run. Any output or LCD
display set to kW Overload Protection is energised. The kW load must fall below
the Return level in order to cancel the output source.
Click to enable or
disable the option.
The relevant values
below will appear
greyed out if the
alarm is disabled.
Click and drag to change the
setting.