Edit Configuration
9
4.2.1 MODULE OPTIONS
Miscellaneous
Options
Enable fast loading
feature
= Normal Operation, the safety on timer will be observed in full. This feature is useful if the
module is to be used with some small engines where pre-mature termination of the delay
timer can lead to overspeed alarms on start up.
= The module will terminate the safety on timer once all monitored parameters have
reached their normal settings. This feature is useful if the module is to be used as a standby
controller as it allows the generator to start and go on load in the shortest possible time.
NOTE: Enabling Fast Loading is only recommended where steps have been
taken to ensure rapid start up of the engine is possible. (For example when fitted with
engine heaters, electronic governors etc.)
Audible alarm prior
to starting
= The module will start with no audible indication
= The module will give an audible warning during the pre-heat timer as an indicator that
the set is about to run. This is often a site’s specification requirement of AUTO mode
operation.
All Warnings Are
Latched
= Normal Operation, the warnings and pre-alarms will automatically reset once the
triggering condition has cleared.
= Warnings and pre-alarms latch when triggered. Resetting the alarm is performed by
either an external reset applied to one of the inputs or, the ‘Stop/Reset’ pushbutton must be
operated (once the triggering condition has been cleared).
Enable sleep mode
=Normal operation
=The module goes into "sleep mode” if left in manual mode for a prolonged time with no
button presses.
Enable manual fuel
pump control
=Normal operation
=Allows manual fuel pump control when the “fuel level” instrument page is being viewed.
Support right-left
languages in
module strings
Determines the direction of text input where supported (i.e. configurable input text)
=left to right language support
=right to left language support
Free entry boxes to allow the user to
give the configuration file a
description. Typically this is used to
enter the job number, customer
name, engineers name etc.
Allows the user to
select the function
of the modules
user configurable
LED indicators.
For details of
possible selections,
please see section
entitled Output
sources elsewhere
in this document.
Allows the user to
create logo and text
insert cards

Table of Contents

Other manuals for Deep Sea Electronics Plc DSE8810

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Deep Sea Electronics Plc DSE8810 and is the answer not in the manual?

Deep Sea Electronics Plc DSE8810 Specifications

General IconGeneral
BrandDeep Sea Electronics Plc
ModelDSE8810
CategoryController
LanguageEnglish

Related product manuals