Edit Configuration
51
4.7.4.4 NEGATIVE PHASE SEQUENCE
(Negative Sequence Current / Unbalanced Load)
Unbalanced loads cause negative sequence current in the alternator stator. These currents cause harmonics
which can eventually lead to overheating and melting of the rotor. An unbalanced load is however, permissible
within limits.
For recommended settings you should contact your alternator manufacturer.
Permitted imbalance of one phase
current to another (Percentage of full
generator current)
Reaction timer
Click to enable or disable the
option. The relevant values
below will appear greyed out
if the alarm is disabled.