Pre alarm
= Pre-alarm is disabled
= If the temperature exceeds the trip setting, an alarm is generated. The temperature
must fall below the return setting to cease the alarm.
Electrical Trip
= Electrical trip is disabled
= If the temperature exceeds the trip setting, an alarm is generated, the load switch is
opened and the module enters the cooling timer after which the set is stopped.
Shutdown
If the temperature exceeds the trip setting, an alarm is generated, the load switch is opened
and the set is immediately stopped.
Click to edit the
‘sensor curve’. See
section entitled Editing