2 Installation
2.7 NET network
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com 55
Figure 56:RJ45 socket
Socket 1 (IN) is used for connecting the incoming data cable from the
physically preceding easyNet station. Socket 2 (OUT) is used for connecting
the outgoing data cable to the physically next easyNet station.
Bus termination resistor
The physically first and last stations in the easyNET network must each be
terminated with a bus termination resistor. Because the physically first
easyNet station has no predecessor, the bus termination resistor is
connected to socket 1 here. Accordingly, the bus termination resistor is
connected to socket 2 of the last easyNet station.
Value: 124
Terminating connector: EASY-NT-R
1
SEL_IN
GND(GROUND)
(E)CAN_L
(E)CAN_H
SEL_OUT
23 41234
1
1
81 8
2
NET
IN OUT