2 Installation
2.7 NET network
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com 57
Prepared by user
The following components are available for assembling different cable
lengths:
• Connection cable
• Type - EASY-NT-CAB, cable 100 m, 4 x 0.18 mm
2
• Bus connection plug
• RJ45 plug, part no.: EASY-NT-RJ45 (8-pole)
• Tools
• Crimping tool for RJ45 plug, part no.: EASY-RJ45-TOOL. AWG 24,
0.2 mm
2
is the largest crimpable cross section.
Cable layout
4-core, twisted pair; → section 12.3.7, “NET network”, page 359.
→
The table on Page 59 provides information for the required cable
cross-section of longer cable lengths, taking the cable
resistance into account.
Cable pair Pen Line
A 1 Data cable ECAN_H
A 2 Data cable ECAN_L
B 3 Ground cable GND (Ground)
B 4 Selection cable SEL (IN/OUT)
→
The most basic easyNet configuration operates with the cables
ECAN_H, ECAN_L, GND. The selection cable is only used for
automatic addressing and configuration.