SLX9000 Adjustable Frequency Drives User Manual
MN04003020E
For more information visit: www.eaton.com 8-9
January 2009
Table 8-5: Basic Parameters P2.1, continued
Input Signals (Control Keypad: Menu P2 P2.2)
Table 8-6: Input Signals, P2.2
Code Parameter Min. Max. Unit Default Cust ID Note
P2.1.19 Preset speed 1 0.00 Par.
2.1.2
Hz 10.00 105
P2.1.20 Preset speed 2 0.00 Par.
2.1.2
Hz 50.00 106
P2.1.21 Automatic restart 0 1 0 731 0 = Not used
1 = Used
P2.1.22 Parameter conceal 0 1 0 115 0 = All parameters and menus
visible
1 = Only group P2.1 and menus M1
to H5 visible
Code Parameter Min. Max. Unit Default Cust ID Note
P2.2.1
Expander board
DIE1 function
0 13 7 368 0 = Not used
1 = Reverse
2 = External fault, cc
3 = External fault, oc
4 = Fault reset
5 = Run enable
6 = Preset speed 1
7 = Preset speed 2
8 = DC-braking command
9 = Motor pot. UP (cc)
10 = Motor pot. DOWN (cc)
11 = Disable PID (PID control
selection)
12 = PID Keypad ref. 2 selection
13 = Interlock 1
P2.2.2
Expander board
DIE2 function
0 13 4 330 Same as parameter 2.2.1, except:
13 = Interlock 2
P2.2.3
Expander board
DIE3 function
0 13 11 369 Same as parameter 2.2.1, except:
13 = Interlock 3
P2.2.4 DIN4 function (AI1) 0 13 2 499 Used if P2.2.6 = 0
Selections same as in parameter 2.2.3
P2.2.5 AI1 signal selection 0 10 377 10 = AI1 (1 = Local, 0 = input 1)
11 = AI2 (1 = Local, 1 = input 2)
20 = Exp. AI1 (2 = exp. board, 0 =
input 1)
21 = Exp AI2 (2 = exp. board, 1 =
input 2)
P2.2.6 AI1 signal range 1 4 3 379 0 = Digital input 4
1 = 0 – 20 mA
2 = 4 – 20 mA
3 = 0 – 10V
4 = 2 – 10V
Not used if AI2 Custom min > 0% or
AI2 custom max. < 100%
Note! See Page 5-22