SLX9000 Adjustable Frequency Drives User Manual
8-14 For more information visit: www.eaton.com
MN04003020E
January 2009
Table 8-11: Protections, P2.7, continued
Autorestart Parameters (Control Keypad: Menu P2 ➔ P2.8)
Table 8-12: Autorestart Parameters, P2.8
Code Parameter Min. Max. Unit Default Cust ID Note
P2.7.8 Motor cooling
factor at zero
speed
0.0 150.0 % 40.0 706
P2.7.9 Motor thermal
time constant
1 200 min 45 707
P2.7.10 Motor duty cycle 0 100 % 100 708
P2.7.11 Stall protection 0 3 1 709 Same as parameter 2.7.1
P2.7.12 Stall current limit 0.1 I
nmotor
x 2
AI
nmotor
x
1.3
710
P2.7.13 Stall time limit 1.00 120.00 s 15.00 711
P2.7.14 Stall frequency
limit
1.0 P2.1.2 Hz 25.0 712
P2.7.15 Underload
protection
0 3 0 713 Same as parameter 2.7.1
P2.7.16 Underload curve
at nominal
frequency
10.0 150.0 % 50.0 714
P2.7.17 Underload curve
at zero frequency
5.0 150.0 % 10.0 715
P2.7.18 Underload
protection time
limit
2.00 600.00 s 20.00 716
P2.7.19 Response to
thermistor fault
0 3 2 732 Same as parameter 2.7.1
P2.7.20 Response to
fieldbus fault
0 3 2 733 Same as parameter 2.7.1
P2.7.21 Response to slot
fault
0 3 2 734 Same as parameter 2.7.1
P2.7.22 Actual value
supervision
0 4 0 735 0 = No response
1 = Warning if below limit
2 = Warning if above limit
3 = Fault, if below limit
4 = Fault, if above limit
P2.7.23 Actual value
supervision limit
0.0 100.0 % 10.0 736
P2.7.24 Actual value
supervision delay
0 3600 s 5 737
Code Parameter Min. Max. Unit Default Cust ID Note
P2.8.1 Wait time 0.10 10.00 s 0.50 717
P2.8.2 Trial time 0.00 60.00 s 30.00 718
P2.8.3 Start function 0 2 0 719 0 = Ramp
1 = Flying start
2 = According to par. 2.4.6