SLX9000 Adjustable Frequency Drives User Manual
MN04003020E
For more information visit: www.eaton.com 5-25
January 2009
Table 5-20: Control Word
In SLX9000 applications, the three first bits of the control word are used to control the drive.
However, you can customize the content of the control word for your own applications
because the control word is sent to the drive as such.
Table 5-21: Speed Reference
This is the Reference 1 to the drive. Used normally as Speed reference. The allowed scaling is
-10000 – 10000. In the application, the value is scaled in percentage of the frequency area
between the set minimum and maximum frequencies.
Table 5-22: Bit Definitions
Fieldbus Parameters
RS-485 Communication Status (I6.10.1)
With this function you can check the status of the RS-485 bus. If the bus is not in use, this
value is 0.
xx.yyy
xx = 0 – 64 (Number of messages containing errors)
yyy = 0 – 999 (Number of messages received correctly)
Fieldbus Protocol (P6.10.2)
With this function you can select the fieldbus communications protocol.
0 = Not used
1 = Modbus protocol
15141312111098765 43210
——————————— —— RSTDIRRUN
15141312111098765 43210
MSB—————————— ————LSB
Bit
Description
Value = 0 Value = 1
RUN Stop Run
DIR Clockwise Counterclockwise
RST Rising edge of this bit will reset active fault
RDY Drive not ready Drive ready
FLT No fault Fault active
W No warning Warning active
AREF Ramping Speed reference reached
Z — Drive is running at zero speed
F — Flux Ready