EasyManua.ls Logo

Eaton SLX9000 - Table 1-8: Technical Information

Eaton SLX9000
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SLX9000 Adjustable Frequency Drives User Manual
MN04003020E
For more information visit: www.eaton.com 1-7
January 2009
Table 1-8: Technical Information
Description Specification
Mains Connection
Input Voltage V
in
208 – 240V; -15% to +10% three-phase
380 – 500V; -15% to +10% three-phase
525 – 690V; -15% to +10% three-phase
Input Frequency 45 – 66 Hz
Connection to Mains Once per minute or less (typical application)
Motor Connection
Output Voltage 0 – V
in
Continuous Output Current I
H
: Ambient temperature max. 122°F (+50°C),
overload 1.5 x I
H
(1 min./10 min.)
I
L
: Ambient temperature max. 104°F (+40°C),
overload 1.1 x I
L
(1 min./10 min.)
Starting Torque 150% (Low overload); 200% (High overload)
Starting Current 2 x IH 2 secs every 20 secs, if output frequency <30 Hz and
temperature of heatsink <+60°C
Output Frequency 0 – 320 Hz
Frequency Resolution .01 Hz
Control Characteristics
Control Method Frequency control V/f
Open Loop Sensorless Vector Control
Switching Frequency
(See Parameter 2.6.8)
208 – 230V: 3/4 – 15 hp: 1 to 16 kHz; default 10 kHz
20 – 30 hp: 1 to 10 kHz; default 3.6 kHz
380 – 500V: 1 – 30 hp: 1 to 16 kHz; default 10 kHz
40 – 60 hp: 1 to 10 kHz; default 3.6 kHz
525 – 690V: All Sizes: 1 to 6 kHz; default 1.5 kHz
Frequency Reference
– Analog Input
– Keypad Reference
Resolution .1% (10-bit), accuracy ±1%
Resolution .01 Hz
Field Weakening Point 30 – 320 Hz
Acceleration Time .1 – 3000 sec.
Deceleration Time .1 – 3000 sec.
Braking Torque DC brake: 30%*T
N
(without brake option)
Ambient Conditions
Ambient Operating Temperature 14°F (-10°C) (no frost) to 122°F (50°C): I
H
14°F (-10°C) (no frost) to 104°F (40°C): I
L
Storage Temperature -40 to 158°F (-40 to 70°C)
Relative Humidity 0 – 95% RH, non-condensing, non-corrosive,
no dripping water
Air Quality:
– Chemical Vapors
– Mechanical Particles
IEC 721-3-3, unit in operation, class 3C2
IEC 721-3-3, unit in operation, class 3S2
Altitude 100% load capacity (no derating) up to 3300 ft. (1000m)
1-% derating for each 330 ft. (100m) above 3300 ft. (1000m);
max. 10000 ft. (3000m)

Table of Contents