SLX9000 Adjustable Frequency Drives User Manual
MN04003020E
For more information visit: www.eaton.com 8-11
January 2009
Output Signals (Control Keypad: Menu P2 P2.3)
Table 8-7: Output Signals, G2.3
Code Parameter Min. Max. Unit Default Cust ID Note
P2.3.1 Relay output 1
function
0 20 3 313 0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = FC overheat warning
6 = Ext. fault or warning
7 = Ref. fault or warning
8 = Warning
9 = Reversed
10 = Preset speed
11 = At speed
12 = Mot. regulator active
13 = OP freq. limit superv.1
14 = Control place: IO
15 = Thermistor fault/ warning
16 = Actual value supervision
17 = Autochange 1 control
18 = Autochange 2 control
19 = Autochange 3 control
20 = AI supervision
P2.3.2 Expander board
relay output 1
function
0 19 2 314 Same as parameter 2.3.1
P2.3.3 Expander board
relay output 2
function
0 19 3 317 Same as parameter 2.3.1
P2.3.4 Expander board
digital output 1
function
0 19 1 312 Same as parameter 2.3.1
P2.3.5 Analog output
function
0 12 1 307 See parameter 2.1.16
P2.3.6 Analog output
filter time
0.00 10.00 s 1.00 308 0 = No filtering
P2.3.7 Analog output
inversion
0 1 0 309 0 = Not inverted
1 = Inverted
P2.3.8 Analog output
minimum
0 1 0 310 0 = 0 mA
1 = 4 mA
P2.3.9 Analog output
scale
10 1000 % 100 311
P2.3.10 Expander board
analog output 1
function
0 12 0 472 Same as parameter 2.1.16
P2.3.11 Expander board
analog output 2
function
0 12 0 479 Same as parameter 2.1.16
P2.3.12 Output frequency
limit 1
supervision
0 2 0 315 0 = No limit
1 = Low limit supervision
2 = High limit supervision
P2.3.13 Output frequency
limit 1;
Supervised value
0.00 Par.
2.1.2
Hz 0.00 316