2.1.17 DIN2 function ID319
This parameter has 10 selections. If digital input DIN2 is not used, set the parameter 
value to 0.
1 Start reverse
2 Reverse
3 Stop pulse
4 External fault
Contact closed: Fault is displayed and motor stopped when the input is 
active
5 External fault
Contact open: Fault is displayed and motor stopped when the input is 
not active
6 Run enable
Contact open: Start of motor disabled
Contact closed: Start of motor enabled
Coast stop if dropped during RUN
7 Preset speed 2
8 Motor potentiometer UP
Contact closed: Reference increases until the contact is opened.
9 Disable the PID-controller (Direct frequency reference)
10 Interlock 1 (can only be selected when pump and fan control is active, 
P2.9.1=2)