SLX9000 Adjustable Frequency Drives User Manual
MN04003020E
For more information visit: www.eaton.com 6-3
January 2009
Test B— Control from the control keypad:
● Change the control from the I/O terminals to the keypad as advised on Page 5-10.
● Press the START button on the keypad.
● Move over to the Keypad Control Menu K3 and Keypad Reference submenu (see
Keypad Reference on Page 5-11) and change the frequency reference with the
Browser up and down buttons.
● Check in Monitoring Menu M1 that the value of Output Frequency changes
according to the change of frequency reference.
● Press the STOP button on the keypad.
9. Run the start-up tests without the motor being connected to the process. If this is not
possible, make sure that running each test is safe prior to running it. Inform your co-
workers of the tests.
● Switch off the supply voltage and wait until the drive has stopped as advised on
Page 6-1, Safety Precautions.
● Connect the motor cable to the motor and to the motor cable terminals of the drive.
● Make sure that all Start/Stop switches are in Stop positions.
● Switch the supply voltage ON.
● Repeat test 8A or 8B.
10. Connect the motor to the process (if the start-up test was run without the motor being
connected).
● Before running the tests, make sure that this can be done safely.
● Inform your co-workers of the tests.
● Repeat test 8A or 8B.