Menu structure of CI 3000
86
Version 2.09 09. April 2014
Page 2 – Configure measuring location
Press the ENTER key to configure the measuring location.
MEASURING POINT Entry Default
Type Power Select meter type: Power, water, gas ↑, ↓ Power
Name of measuring location Enter freely editable name (max. 19 characters)
A name should always be entered for the measuring
location!
Text
Item ID XXXXX Enter a freely editable item identification (ID)
(max. 5 characters)
-
Meter Input
.Module XXXXX
.Channel k
Configuration of meter input (required entrie !)
XXXX: Name of module
(Int.I / SIOX n=1 to 4)
k: Channel No. to which meter signal is transmitted
↑, ↓, number -
XXXXX
Tariff Input
.Module XXXXX
.Channel k
Configure tariff input,
XXXX: Name of module
(Int.I / SIOX n=1 to 4)
k: Channel No. to which optional tariff signal is
transmitted
-
Sync Input
.Module XXXXX
.Channel k
Configure sync input,
XXXX: Name of module
(Int.I / SIOX n=1 to 4)
k: Channel No. to which synchronizing signal is
transmitted
-
Record. power X Specifies whether a load profile is recorded for the
M bus meter
Y/N N
Meter No. xxxxxxxxxxx Enter Meter No. (max. 10 characters) ↑, ↓, number -
Unit kWh Select unit of measurement: kWh, m
3
↑, ↓ -
Pulses/Unit XXXX Only for impulse meters:
Enter meter constant (pulses per kWh or m
3
)
1 to 9999
M bus meter:
Must be set on the meter!
↑, ↓, number -
Transf.Factor XXX Only for impulse meters:
Enter conversion ratio of current transformer: 1 to 255
M bus meter:
Must be set on the meter!
10
delete Delete measuring location:
Displays prompt: Are you sure? No: ESC Yes: ↵
↵, ESC 1