SERVICE
GAS CONVERSION
The BASO combination gas valve contains a bypass orice which is not EDGE approved
for eld replacement.
Gas conversions require replacement of the BASO combination gas valve, main orice,
and the adjustment of the air shutter. Parts and labor costs incurred for gas conversions
are not covered by the limited warranty.
NOTICE
ORIFICE SIZING CHART
MAIN ORIFICE PILOT BYPASS
BTU’S
65,000 80,000 125,000 150,000 185,000 LP NAT
LP
(10K)
NAT
(10K)
SIZE 0.0890 0.1405 0.1015 0.1540 0.1200 0.1910 0.1360 0.2090 0.1540 0.2323 0.025 0.039 0.039 0.059
P/N 135069 135068 135075 135074 135071 135070 135073 135072 135067 135066 (7225) (3239) #61 #53
1830-P
X X X
1830-N
X X X
2440-P
X X X
2440-N
X X X
MAIN ORIFICE PILOT BYPASS
BTU’S
65,000 80,000 125,000 150,000 185,000 LP NAT
LP
(25K)
NAT
(25K)
SIZE 0.0890 0.1405 0.1015 0.1540 0.1200 0.1910 0.1360 0.2090 0.1540 0.2323 0.025 0.039 0.059 0.093
P/N 135069 135068 135075 135074 135071 135070 135073 135072 135067 135066 (7225) (3239) #53 3/32"
3240-P
X X X
3240-N
X X X
2460-P
X X X
2460-N
X X X
3260-P
X X X
3260-N
X X X
3860-P
X X X
3860-N
X X X
4460-P
X X X
4460-N
X X X
3270-P
X X X
3270-N
X X X
3870-P
X X X
3870-N
X X X
P = Propane N = Natural Gas