EasyManuals Logo

EIM TEC2000 User Manual

EIM TEC2000
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
2. Quick Start
TEC 2000 Installation & Operation Manual E2K-405-0902
2-5
2.2. Network Setup
This is only applicable if the Controlinc Auxiliary Control Module (ACM) and the
Communication Adapter Module (CAM) are installed and enabled. These instructions
assume all parameters have been set with the exception of the network node address.
1. Remain in the “SETUP” mode.
2. Select NEXT to advance through the displays until “NETWORK SETUP?” appears.
3. Rotate the control knob to YES. “NETWORK NODE ADDRESS XXX” appears.
4. Rotate the control knob to NO to increment the address numbers. Hold in the NO
position until the desired address is reached.
NOTE: If the desired address is a lower number than what is displayed, continue to
increment the numbers until the highest numbered address is reached. The address
numbers will then start with the lowest numbered address and continue to increment.
5. When the correct address is displayed, rotate the control knob to YES.
2.3. Check Settings
1. Operate the valve to the fully close position.
2. Verify the green LED is ON (default setting) and 0% is displayed.
3. Operate the valve to the fully open position.
4. Verify the red LED is ON (default setting) and 100% is displayed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EIM TEC2000 and is the answer not in the manual?

EIM TEC2000 Specifications

General IconGeneral
BrandEIM
ModelTEC2000
CategoryController
LanguageEnglish

Related product manuals