3. Installation
TEC 2000 Installation & Operation Manual E2K-405-0902
3-18
3.8.3. Two RDMs (one 24Vdc and one 115/208/220/230 Vac power source)
To use two RDMs with one actuator, connect as detailed in Table 3-9.
Table 3-9 Two RDMs Connected to the Actuator
RMD RDM Terminal
Block Number
Function TEC 2000
Terminal Block
Number
Cable Type-
Belden or
Equivalent
Line 115/230 Vac 50/60 Hz (+) - 20AWG or Larger
Neu 0V Common - 20AWG of Larger
3 RS-485 (+) 21
1 RS-485 (-) 23
RDM #1
2 Shield 24
Belden 9841
6 24 Vdc 9=0 9
5 0V Common 10
Belden
8719
3 RS-485 (+) 21
1 RS-485 (-) 23
RDM #2
2 Shield 24
Belden
9841
Belde
n
8723