5. Customizing Actuator Settings
TEC 2000 Installation & Operation Manual E2K-405-0902
5-25
5.6.9. Network Setup (CAM and Controlinc ACM Required)
NOTE: Only displayed/applicable if the Communication Adapter Module (CAM) and the
ControIinc ACM are installed, and the network control is enabled. See Section 5.6.2, Valve
Control Setup.
1. At the “NETWORK SETUP?” prompt, answer “YES.”
2. Use the selector knob (NEXT/BACK) to review the settings for network control.
3. Use the control knob (NO) to increment the node address, response delay, and analog I/O
scale, and to select the parity, and analog scale.
4. Answer “YES” after each selection.
See Figure 5-14.
Protocol selection is displayed for information only. Protocol is set at the factory by the
selected CAM based on purchase order information. Protocol may not be changed by the
user in the field. Only factory technicians may change the CAM or protocol in the field.
Baud rate is automatically detected by the Controlinc ACM and no setup is required.
To calibrate analog inputs, the user must connect a calibrated precision 4-20mA current
source to Terminals 25(+) and 26(-) for AIN#1 or Terminals 27(+) and 28 (-) for AIN#2. To
calibrate analog output, the user must connect a calibrated precision 4-20mA current meter to
Terminals 29(+) and 30(-) for AO#1.