5. Customizing Actuator Settings
TEC 2000 Installation & Operation Manual E2K-405-0902
5-2
5 Customizing Actuator Settings
5.1. Entering Setup Mode
The “SETUP” mode must be entered to modify any configuration settings.
1. Place the selector knob in the STOP position. Setup may be performed at any one
location; i.e. at the LDM or any RDM that is connected.
NOTE: STOP button on the Clicker only stops a moving valve.
2. Rotate the control knob to YES, then NO, then YES, then NO in rapid succession and
then release. “SETUP” icon will be displayed on the display module and “SETUP?” will
be displayed on the message center.
NOTE: Do not hold the knob in any one position longer than 0.5 seconds.
3. Rotate the control knob to YES. A series of questions will be displayed as detailed in
Figure 5-1.
NOTE: If the control knob is placed in the NO position or if NEXT or BACK is selected in
lieu of YES the display will return to the normal display mode.
4. Use the control knob to answer “YES” or “NO” to the displayed questions. Use the
selector knob, NEXT and BACK, to advance through the setup selections.
5. When configuring is complete, advance to “EXIT SETUP?” Answer “YES.” The display
will return to normal display model.
NOTE: If a knob entry is not made within 120 seconds, the actuator will exit the “SETUP”
mode and revert to the normal display.