EasyManua.ls Logo

EIM TEC2000 - Network Controlled

EIM TEC2000
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3. Installation
TEC 2000 Installation & Operation Manual E2K-405-0902
3-14
Figure 3-16 External VFD Control Wiring
3.6.4. Network Controlled
For the actuator to be network controlled, a Controlinc ACM and a Communication Adapter
Module (CAM) must be installed. Each CAM is required for a specific protocol and network
topology, and enables the network capability. To install the Controlinc ACM see Section
3.6.1, Wiring the ACM.
NOTE: Factory personnel must install the ACM and CAM. These modules (CAMs) may be
installed in the field only by factory-trained technicians using a special passcode to enter the
FACTORY SETUP” mode.
Connect the actuators as shown in Table 3-5 for RS-485 redundant bus or E>Net networks.
If another protocol is selected then refer to the wiring diagram supplied with the actuator for
connections.
NOTE: If E>Net network topology is specified, insert a jumper between Terminals 40 and 42
to connect the network cable shield throughout the network and connect a single point earth
ground elsewhere.
See Section 3.3, Electrical Connections for general electrical connection requirements.

Table of Contents

Related product manuals