11
GB
Product information about the directive 2009/125/EG and regulation (EU) 813/2013
THISION L Icon Unit 50 65 65 L 85 100 120 145
Condensing boiler - - Yes Yes Yes Yes Yes Yes Yes
Low-temperature boiler - - No No No No No No No
B1 boiler - - No No No No No No No
Cogeneration space heater - - No No No No No No No
Combination heater - - No No No No No No No
ErP Heating
Rated heat boiler P
rated
kW 46 61 56 81 93 112 132
At rated heat output and high-tempera-
ture regime
P4 kW 45.7 60.8 56,4 81.1 92.9 111.6 132.2
At 30 % of rated heat output and
lowtemperature regime 1)
P1 kW 15.1 20.0 18,6 26.8 30.6 36.7 43.5
Seasonal space heating energy effi-
ciency
Ks % 92 92 92 92 92 92 92
At rated heat output and high-temperatu-
re regime 2)
K4 % 87.7 87.7 87,7 87.7 87.9 87.9 87.9
At 30 % of rated heat output and low
temperature regime 1)
K1 % 96.5 96.5 96,5 96.5 96.5 96.5 96.5
Auxiliary electricity consumption
At full load elmax kW 0.100 0.100 0,100 0.214 0.214 0.214 0.221
At rated heat output and high-tempera-
ture regime
elmin kW 0.025 0.025 0,025 0.038 0.038 0.038 0.043
At 30 % of rated heat output and
lowtemperature regime 1)
P
SB kW 0.003 0.003 0,003 0.003 0.003 0.003 0.003
Supplementary heater
Standby heat loss Pstby kW 0.122 0.122 0,122 0.122 0.122 0.122 0.122
Ignition burner power consumption P
ign kW 0.000 0.000 0,000 0.000 0.000 0.000 0.000
Emissions of nitrogen oxides NO
X mg/kWh39393939393939
1) by return temperature 30°C
2) by return temperature and feed temperature (60-80°C)
Product information ErP
THISION L

Table of Contents