EasyManuals Logo

elco THISION L User Manual

elco THISION L
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
19
GB
Air / Flue pipe data
Concentric pipe nominal diam.
Ø100/150
Tolerance female Ø internal
101 mm
150 mm
Single pipe nominal diam.
Ø100
Tolerance female Ø internal
101
±0.7
mm
Ø130
Tolerance female Ø internal
131
±0.7
mm
Material
PP (Concentric flue pipe) - Galva 0,4/Alluminium 1,3mm (Concentric air intake
pipe)
PP (single pipe)
Material seal
EPDM black for corrosion class 1 / Viton for corrosion class 2
Heat resistance
0 W/m
2
K
Wall thickness
2.2 mm
Temperature class:
T120
Pressure class:
P1 max. 200Pa / H1 max. 5000Pa
Corrosion class:
W1
Location class
Concentric pipe: Only outside buildings / Single pipe: Only inside buildings
Fire rating class
E
Outer wall class
(Concentric pipe only) L0
Distance to combustible materials
Concentric pipe: 00 mm / Single pipe: 30 mm
+1.0
- 0.5
+1.0
- 0.5
Installation
Air/Flue gas system
Flue Gas data
Boiler
type
Nominal heat
output
Nominal heat
input
Flue
gas
connection
(DN)
CO
Level
Flue gas
temperature
Flue gas
quantity
Max
permissible
ÀXH
resistance
kW kW mm % °C g/s Pa
THISION L
max min max min max min max min max min max min
50 45.7 7.7 46.9  100
  76 33
26 4 150 15
65  10.1 62.4 10.4 100 35 6 150 15
  13.4   100 47 7 150 15
100 92.9 15.6 95.2 16.0 100 52 9 150 15
120 111.6  114.3 19.2 100 62 11 200 15
145 132.2 23.3 135.5 23.9 130 74 12 200 15
65L 56.4 10.1 57.9 10.4 100 35 6 150 15