Verify Power Readings
This p age d isplays s pecific v alues f or t he different Electrical P ower P arameters
relevant t o t he Specific P ower C onfiguration. Fo r a f ull d escription o n a ll t he
definitions & subsequent parameter calculations see Power.
Access your G4K Unit via the Web Interface Open Monitoring Power:
Verify your Configurations in this window that displays:
Reactive Power
Active Power
Apparent Power
True & Displacement Power Factor
In m ost network c onfigurations th e Active Power will reflect a Positive
Value. S hould i t h ave a Negative Value, recheck y our Voltage & Current
Polarity Configuration. I n the presence of a g enerator, the Active Power
will reflect a Negative Value.