B − 14
Appendix B Communication Tables
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
Table B-19. Alarms/Trips Block (Page 2)
Ethernet IP
Address
Modbus
Address
Alarms/Trips (Page 2) Data Type Value Mode
Lower
Range
Higher
Range
N66:0 40430 Low Suction Temperature Alarm F-INT
Read-
Write
-100 210
N66:1 40431 Low Suction Temperature Trip F-INT
Read-
Write
-100 210
N66:2 40432 High Discharge Temperature Alarm F-INT Read NA NA
N66:3 40433 High Discharge Temperature Trip F-INT Read NA NA
N66:4 40434 Low Crankcase Oil Temperature - Start Alarm F-INT Read NA NA
N66:5 40435 Low Crankcase Oil Temperature - Start Trip F-INT Read NA NA
N66:6 40436 Low Crankcase Oil Temperature - Run Alarm F-INT Read NA NA
N66:7 40437 Low Crankcase Oil Temperature - Run Trip F-INT Read NA NA
N66:8 40438 High Crankcase Oil Temperature Alarm F-INT Read NA NA
N66:9 40439 High Crankcase Oil Temperature Trip F-INT Read NA NA
Table B-20. Alarms/Trips Block (Page 3)
Table B-21. Timers Block (Page 1)
Ethernet IP
Address
Modbus
Address
Alarms/Trips (Page 3) Data Type Value Mode
Lower
Range
Higher
Range
N67:0 40460 Low Oil Pressure Alarm F-INT Read NA NA
N67:1 40461 Low Oil Pressure Trip F-INT Read NA NA
N67:2 40462 High Filter Diff. Pressure - Start Alarm F-INT Read NA NA
N67:3 40463 High Filter Diff. Pressure - Start Trip F-INT Read NA NA
N67:4 40464 High Filter Diff. Pressure - Run Alarm F-INT Read NA NA
N67:5 40465 High Filter Diff. Pressure - Run Trip F-INT Read NA NA
N67:6 40466 High Motor Amps Alarm F-INT Read NA NA
N67:7 40467 High Motor Amps Trip F-INT Read NA NA
Ethernet IP
Address
Modbus
Address
Timers (Page 1) Data Type Value Mode
Lower
Range
Higher
Range
N68:0 40500 Load Increase Start Delay (seconds) INT Read NA NA
N68:1 40501 Compressor Interlock Bypass (seconds) INT Read NA NA
N68:2 40502 Low Oil Pressure Diff. Bypass (seconds) INT Read NA NA
N68:3 40503
Low Crankcase Oil Temperature Changeover
(seconds)
INT Read NA NA
N68:4 40504 High Discharge Temperature Bypass (seconds) INT Read NA NA
N68:5 40505 High Filter Diff. Pressure Changeover (seconds) INT Read NA NA
N68:6 40506 High Motor Amps Bypass (seconds) INT Read NA NA