B − 15
Appendix B • Communication Tables
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
Table B-23. Conguration (Time) Block
Ethernet IP
Address
Modbus
Address
Conguration
(Time)
Data Type Value Mode
Lower
Range
Higher
Range
N70:0 40600 Time – Hours INT (HH) Read-Write 0 23
N70:1 40601 Time – Min INT (MM) Read-Write 0 59
N70:2 40602 Time – Secs INT (SS) Read-Write 0 59
N70:3 40603 Date – Year INT (YYYY) Read-Write 1970 2037
N70:4 40604 Date – Month INT (1-12) Read-Write 1 12
N70:5 40605 Date – Day INT (1-31) Read-Write 1 31
Table B-22. Timers Block (Page 2)
Ethernet IP
Address
Modbus
Address
Timers (Page 2) Data Type Value Mode
Lower
Range
Higher
Range
N69:0 40520
Communication Failure Detect Timer
(minutes)
INT Read NA NA
N69:1 40521 Restart On Power Failure Timer (minutes) INT
Read-
Write
1 120
N69:2 40522 True Anti-Recycle Timer (minutes) INT
Read-
Write
6 60
N69:3 40523
Accumulative Anti-Recycle Timer (min-
utes)
INT
Read-
Write
6 60
N69:4 40524 Hot Starts per Hour INT
Read-
Write
1 10
N69:5 40525
Oil Recovery Solenoid Shutoff Delay
(seconds)
INT Read NA NA
N69:6 40526 Low Oil Level Alarm Delay (seconds) INT Read NA NA
N69:7 40527 Low Oil Level Trip Delay (seconds) INT Read NA NA