Commissioning Proline Prowirl F 200 PROFIBUS PA
110 Endress+Hauser
Parameter Prerequisite Description Selection / User
entry
Factory setting
Temperature unit – Select temperature unit.
Effect
The selected unit applies for:
• Temperature
• Maximum value
• Minimum value
• Average value
• Maximum value
• Minimum value
• Maximum value
• Minimum value
• 2nd temperature delta heat
• Fixed temperature
• Reference combustion
temperature
• Reference temperature
• Saturation temperature
Unit choose list Country-specific:
• °C
• °F
Minimum frequency value The Frequency option is
selected in the Operating
mode parameter, and one of
the following options is
selected in the Assign
frequency output parameter
(→ 109):
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam
pressure
*
• Steam quality
*
• Total mass flow
*
• Energy flow
*
• Heat flow difference
*
Enter minimum frequency. 0 to 1 000 Hz 0 Hz
Maximum frequency value The Frequency option is
selected in the Operating
mode parameter, and one of
the following options is
selected in the Assign
frequency output parameter
(→ 109):
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam
pressure
*
• Steam quality
*
• Total mass flow
*
• Energy flow
*
• Heat flow difference
*
Enter maximum frequency. 0 to 1 000 Hz 1 000 Hz