Commissioning Proline Prowirl F 200 PROFIBUS PA
110 Endress+Hauser
Parameter Prerequisite Description Selection / User
entry
Factory setting
Temperature unit Select temperature unit.
Effect
The selected unit applies for:
Temperature
Maximum value
Minimum value
Average value
Maximum value
Minimum value
Maximum value
Minimum value
2nd temperature delta heat
Fixed temperature
Reference combustion
temperature
Reference temperature
Saturation temperature
Unit choose list Country-specific:
°C
°F
Minimum frequency value The Frequency option is
selected in the Operating
mode parameter, and one of
the following options is
selected in the Assign
frequency output parameter
(→  109):
Volume flow
Corrected volume flow
Mass flow
Flow velocity
Temperature
Calculated saturated steam
pressure
*
Steam quality
*
Total mass flow
*
Energy flow
*
Heat flow difference
*
Enter minimum frequency. 0 to 1 000 Hz 0 Hz
Maximum frequency value The Frequency option is
selected in the Operating
mode parameter, and one of
the following options is
selected in the Assign
frequency output parameter
(→  109):
Volume flow
Corrected volume flow
Mass flow
Flow velocity
Temperature
Calculated saturated steam
pressure
*
Steam quality
*
Total mass flow
*
Energy flow
*
Heat flow difference
*
Enter maximum frequency. 0 to 1 000 Hz 1 000 Hz