Diagnostics and troubleshooting Proline Prowirl F 200 PROFIBUS PA
160 Endress+Hauser
Diagnostic information Remedy instructions Influenced measured
variables
No. Short text
494 Switch output simulation Deactivate simulation switch output • Calculated saturated
steam pressure
• Energy flow
• Flow velocity
• Heat flow difference
• Low flow cut off
• Mass flow
• Total mass flow
• Switch output status
• Corrected volume flow
• Steam quality
• Temperature
• Volume flow
Measured variable status
Quality Good
Quality substatus Function check
Coding (hex) 0xBC to 0xBF
Status signal C
Diagnostic behavior Warning
Diagnostic information Remedy instructions Influenced measured
variables
No. Short text
495 Simulation diagnostic event Deactivate simulation –
Measured variable status
Quality Good
Quality substatus Ok
Coding (hex) 0x80 to 0x83
Status signal C
Diagnostic behavior Warning
Diagnostic information Remedy instructions Influenced measured
variables
No. Short text
497 Simulation block output Deactivate simulation –
Measured variable status
Quality Good
Quality substatus Ok
Coding (hex) 0x80 to 0x83
Status signal C
Diagnostic behavior Warning
Diagnostic information Remedy instructions Influenced measured
variables
No. Short text
538 Flow computer configuration incorrect Check input value (pressure, temperature) • Calculated saturated
steam pressure
• Density
• Energy flow
• Heat flow difference
• Low flow cut off
• Mass flow
• Total mass flow
• Switch output status
• Pressure
• Reynolds number
• Specific volume
• Corrected volume flow
• Steam quality
• Degrees of superheat
Measured variable status
Quality Good
Quality substatus Function check
Coding (hex) 0xBC to 0xBF
Status signal S
Diagnostic behavior Warning