Commissioning Proline Promag H 300 PROFINET
98 Endress+Hauser
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Minimum frequency value The Frequency option is
selected in the Operating
mode parameter (→ 95)
and a process variable is
selected in the Assign
frequency output parameter
(→ 97).
Enter minimum frequency. 0.0 to 10 000.0 Hz 0.0 Hz
Maximum frequency value The Frequency option is
selected in the Operating
mode parameter (→ 95)
and a process variable is
selected in the Assign
frequency output parameter
(→ 97).
Enter maximum frequency. 0.0 to 10 000.0 Hz 10 000.0 Hz
Measuring value at minimum
frequency
The Frequency option is
selected in the Operating
mode parameter (→ 95)
and a process variable is
selected in the Assign
frequency output parameter
(→ 97).
Enter measured value for
minmum frequency.
Signed floating-point
number
Depends on country
and nominal
diameter
Measuring value at maximum
frequency
The Frequency option is
selected in the Operating
mode parameter (→ 95)
and a process variable is
selected in the Assign
frequency output parameter
(→ 97).
Enter measured value for
maximum frequency.
Signed floating-point
number
Depends on country
and nominal
diameter
Failure mode The Frequency option is
selected in the Operating
mode parameter (→ 95)
and a process variable is
selected in the Assign
frequency output parameter
(→ 97).
Define output behavior in
alarm condition.
• Actual value
• Defined value
• 0 Hz
0 Hz
Failure frequency The Frequency option is
selected in the Operating
mode parameter (→ 95)
and a process variable is
selected in the Assign
frequency output parameter
(→ 97).
Enter frequency output value
in alarm condition.
0.0 to 12 500.0 Hz 0.0 Hz
Invert output signal – Invert the output signal. • No
• Yes
No