EasyManua.ls Logo

Endress+Hauser Proline Promag W 400 - Page 104

Endress+Hauser Proline Promag W 400
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation Proline Promag W 400 EtherNet/IP
104 Endress+Hauser
x-axis: depending on the number of channels selected displays 250 to 1000 measured
values of a process variable.
y-axis: displays the approximate measured value span and constantly adapts this to the
ongoing measurement.
If the length of the logging interval or the assignment of the process variables to the
channels is changed, the content of the data logging is deleted.
Navigation
"Diagnostics" menu → Data logging
"Data logging" submenu
Data logging
Assign channel 1
Assign channel 2
Assign channel 3
Assign channel 4
Logging interval
Clear logging data
Display channel 1
Display channel 2
Display channel 3
Display channel 4
Parameter overview with brief description
Parameter Description Selection / User entry Factory setting
Assign channel 1 to 4 Assign process variable to logging channel. Off
Volume flow
Mass flow
Flow velocity
Conductivity
Electronic temperature
Off
Logging interval Define the logging interval for data logging.
This value defines the time interval between
the individual data points in the memory.
1.0 to 3 600.0 s 10.0 s
Clear logging data Clear the entire logging data. Cancel
Clear data
Cancel