Proline Promag W 400 EtherNet/IP Technical data
Endress+Hauser 135
Current consumption Transmitter
Order code for "Power supply" Maximum
Current consumption
Maximum
switch-on current
Option L: AC 100 to 240 V 145 mA 25 A (< 5 ms)
Option L: AC/DC 24 V 350 mA 27 A (< 5 ms)
Power supply failure • Totalizers stop at the last value measured.
• Configuration is retained in the plug-in memory (HistoROM DAT).
• Error messages (incl. total operated hours) are stored.
Electrical connection
Potential equalization → 44
Terminals Transmitter
• Supply voltage cable: plug-in spring terminals for wire cross-sections
0.5 to 2.5 mm
2
(20 to 14 AWG)
• Signal cable: plug-in spring terminals for wire cross-sections
0.5 to 2.5 mm
2
(20 to 14 AWG)
• Electrode cable: spring terminals for wire cross-sections 0.5 to 2.5 mm
2
(20 to 14 AWG)
• Coil current cable: spring terminals for wire cross-sections
0.5 to 2.5 mm
2
(20 to 14 AWG)
Sensor connection housing
Spring terminals for wire cross-sections0.5 to 2.5 mm
2
(20 to 14 AWG)
Cable entries Cable entry thread
• M20 x 1.5
• Via adapter:
– NPT ½"
– G ½"
Cable gland
• For standard cable: M20 × 1.5 with cable 6 to 12 mm (0.24 to 0.47 in)
• For reinforced cable: M20 × 1.5 with cable 9.5 to 16 mm (0.37 to 0.63 in)
If metal cable entries are used, use a grounding plate.
Cable specification
16.6 Performance characteristics
Reference operating
conditions
In accordance with DIN EN 29104
• Medium temperature: +28 ± 2 °C (+82 ± 4 °F)
• Ambient temperature: +22 ± 2 °C (+72 ± 4 °F)
• Warm-up period:30 min