Proline Promag W 400 EtherNet/IP Technical data
Endress+Hauser 131
Operable flow range Over 1000 : 1
For custody transfer, the operable flow range is 100 : 1 to 250 : 1, depending on the
nominal diameter. Further details are specified by the applicable approval.
Input signal External measured values
Various pressure transmitters and temperature measuring devices can be ordered
from Endress+Hauser: see "Accessories" section →  127
It is recommended to read in external measured values to calculate the following measured
variables:
Corrected volume flow
Fieldbuses
The measured values are written from the automation system to the measuring device via
EtherNet/IP.
16.4 Output
Output signal EtherNet/IP
Standards In accordance with IEEE 802.3
Signal on alarm Depending on the interface, failure information is displayed as follows:
EtherNet/IP
Device diagnostics Device condition can be read out in Input Assembly
Local display
Plain text display With information on cause and remedial measures
Backlight Red backlighting indicates a device error.
Status signal as per NAMUR recommendation NE 107
Operating tool
Via digital communication:
EtherNet/IP
Via service interface
Plain text display With information on cause and remedial measures
Web browser
Plain text display With information on cause and remedial measures