Diagnostics and troubleshooting Proline Promag W 400 EtherNet/IP
116 Endress+Hauser
Diagnostic
number
Short text Remedy instructions Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
842 Process limit Low flow cut off active!
1. Check low flow cut off
configuration
S Warning
862 Empty pipe 1. Check for gas in process
2. Adjust empty pipe detection
S Warning
882 Input signal 1. Check input configuration
2. Check external device or process
conditions
F Alarm
937 EMC interference Change main electronic module S Warning
1)
938 EMC interference 1. Check ambient conditions
regarding EMC influence
2. Change main electronic module
F Alarm
990 Special event 4 Contact service F Alarm
1) Diagnostic status is changeable.
12.9 Pending diagnostic events
The Diagnostics menu allows the user to view the current diagnostic event and the
previous diagnostic event separately.
To call up the measures to rectify a diagnostic event:
Via local display →  110
Via Web browser →  111
Via "FieldCare" operating tool →  113
Other pending diagnostic events can be displayed in the Diagnostic list