Commissioning Proline Promag W 400 EtherNet/IP
98 Endress+Hauser
parameters automatically after 60 s if the user skips back to the operational display mode
from the navigation and editing view.
If write access is activated via access code, it can be also be deactivated only via the
access code →  62.
The user role with which the user is currently logged on via the local display
→  62 is indicated by the Access status display parameter. Navigation path:
"Operation" menu → Access status display
Parameters which can always be modified via the local display
Certain parameters that do not affect the measurement are excepted from write protection
via the local display. Despite the defined access code, these parameters can always be
modified even if the other parameters are locked.
Defining the access code via the Web browser
1. Navigate to the "Enter access code" parameter.
2. Max. Define a max. 4-digit numeric code as an access code.
3. Enter the access code again to confirm the code.
The Web browser switches to the login page.
If no action is performed for 10 minutes, the Web browser automatically returns to
the login page.
The user role with which the user is currently logged on via the Web browser is
indicated by the Access status tooling parameter.
Navigation path: "Operation" menu → Access status tooling
10.10.2 Write protection via write protection switch
Unlike write protection via a user-specific access code, this allows write access to the entire
operating menu - other than the "Contrast display" parameter - to be locked.
The parameter values are now read only and cannot be edited any more (exception
"Contrast display" parameter):
Via local display
1
2
3
4
1
2
3
4
1
2
ON OFF
Default Ethernet network settings
IP 192.168.1.212
Write protection
128
64
32
16
8
4
2
1
IP Address
setting
(last octet)
A0023059
1. Loosen the 4 fixing screws on the housing cover and open the housing cover.