Commissioning Proline Promag W 400 EtherNet/IP
84 Endress+Hauser
Parameter overview with brief description
Parameter Prerequsite Description Selection / User
entry
Factory setting
Format display – Select how measured values
are shown on the display.
• 1 value, max. size
• 1 bargraph + 1
value
• 2 values
• 1 value large + 2
values
• 4 values
1 value, max. size
Value 1 display – Select the measured value that
is shown on the local display.
• Volume flow
• Mass flow
• Conductivity
• Temperature
• Electronic
temperature
• Totalizer 1
• Totalizer 2
• Totalizer 3
Volume flow
0% bargraph value 1 – Enter 0% value for bar graph
display.
Signed floating-point
number
0 l/h
100% bargraph value 1 – Enter 100% value for bar
graph display.
Signed floating-point
number
0.025 l/h
Value 2 display – Select the measured value that
is shown on the local display.
Picklist (see 1st
display value)
None
Value 3 display – Select the measured value that
is shown on the local display.
Picklist (see 1st
display value)
None
0% bargraph value 3 An option was selected in the
Value 3 display parameter.
Enter 0% value for bar graph
display.
Signed floating-point
number
0
100% bargraph value 3 An option was selected in the
Value 3 display parameter.
Enter 100% value for bar
graph display.
Signed floating-point
number
0
Value 4 display – Select the measured value that
is shown on the local display.
Picklist (see 1st
display value)
None
10.6.5 Configuring the low flow cut off
The Low flow cut off wizard guides you systematically through all the parameters that
have to be set for configuring the low flow cut off.
Navigation
"Setup" menu → Low flow cut off