Proline Promag W 400 EtherNet/IP Commissioning
Endress+Hauser 85
Structure of the wizard
Volume flow
Assign variable
Off value
End of wizard
Off
On value
Mass flow
Pres. shock sup.
A0020524-EN
25 "Low flow cut off" wizard in the "Setup" menu
Parameter overview with brief description
Parameter Description Selection / User entry Factory setting
Assign process variable Select process variable for low flow cut off. • Off
• Volume flow
• Mass flow
Volume flow
On value low flow cutoff Enter on value for low flow cut off. Signed floating-point number 0 l/h
Off value low flow cutoff Enter off value for low flow cut off. 0 to 100.0 % 50 %
Pressure shock suppression Enter time frame for signal suppression (=
active pressure shock suppression).
0 to 100 s 0 s