Proline Promag W 400 EtherNet/IP Electrical connection
Endress+Hauser 37
Coil current cable
Standard cable
2 ×0.75 mm
2
(18 AWG) with common, braided copper shield ( ~ 7 mm (0.28"))
and individually shielded cores
Conductor resistance ≤37 Ω/km (0.011 Ω/ft)
Capacitance: core/core,
shield grounded
≤120 pF/m (37 pF/ft)
Operating temperature –20 to +80 °C (–68 to +176 °F)
Test voltage for cable
insulation
≤ AC 1433 V r.m.s. 50/60 Hz or ≥ DC 2026 V
1
2
3
4
5
6
7
a b
A0003194
 9 Cable cross-section
a Electrode cable
b Coil current cable
1 Core
2 Core insulation
3 Core shield
4 Core jacket
5 Core reinforcement
6 Cable shield
7 Outer jacket
Reinforced connecting cables
Reinforced connecting cables with an additional, reinforcing metal braid should be used
for:
When laying the cable directly in the ground
Where there is a risk of damage from rodents
If using the device below IP68 degree of protection
Operation in zones of severe electrical interference
The measuring system meets the general safety requirements →  159 and EMC
specifications →  138.
Grounding is by means of the ground terminal provided for the purpose inside the
connection housing. The stripped and twisted lengths of cable shield to the ground
terminal must be as short as possible.
Cable diameter
Cable glands supplied:
For standard cable: M20 × 1.5 with cable 6 to 12 mm (0.24 to 0.47 in)
For reinforced cable: M20 × 1.5 with cable 9.5 to 16 mm (0.37 to 0.63 in)
(Plug-in) spring terminals for wire cross-sections 0.5 to 2.5 mm
2
(20 to 14 AWG)