COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Unsol Time
Range
0 ~ 255 sec
Default
5
Step
1 sec
Set a delay time of transmission of event data after the last event
occurs.
COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Unsol Type
Range
NOTRIG, PERIOD
Default
NOTRIG
Step
~
Set a type to configure a method to send event data.
NOTRIG : If there is no more event occurrence during setting “Unsol
Time” after the last event occurs, the event data is transmitted.
PERIOD : Unsolicited message is sent to a master with whole event
data occurring after setting “Unsol Time” starting and elapsing when
the first event occurs.
COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Class 1
Range
DISABLE, ENABLE
Default
DISABLE
Step
~
Select the unsolicited response mode of Class 1 events.
COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Class 2
Range
DISABLE, ENABLE
Default
DISABLE
Step
~
Select the unsolicited response mode of Class 2 events.
COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Class 3
Range
DISABLE, ENABLE
Default
DISABLE
Step
~
Select the unsolicited response mode of Class 3 events.
[DNP3.0-1]
Class 1: DISABLE
Class 2: DISABLE
>Class 3: DISABLE
[DNP3.0-1]
>Class 1: DISABLE
>Class 2: DISABLE
>Class 3: DISABLE
[DNP3.0-1]
>Class 1: DISABLE
Class 2: DISABLE
>Class 3: DISABLE
[DNP3.0-1]
>PowUpUnsol: ENABLE
>Unsol Time: 5
>Unsol Type: NOTRIG
[DNP3.0-1]
>Multi Inter: 0.10
>PowUpUnsol: ENABLE
>Unsol Time: 5