Use the Panel Operator of the Drive
The following are the steps to execute the load inertia identification by using the Panel Operator.
Step 1 Press [M] key several times to select the Utility Function Mode.
Step 2 Press [▲] key or [▼] key to select the function number Fn009.
Step 3 Press [◄] key, and Panel Operator displays as below.
Step 4 Press [M] key to execute the load inertia identification.
At this time, Panel Operator displays the speed of the Motor in real time.
Step 5 When this operation has been completed, Panel Operator will display the detection result (Unit: %).
NOTE: You can press the [M] key several times to execute this operation until the detection result is confirmed.
Step 6 Press [▲] key to write the detection value to the parameter Pn106 (Load Inertia Percentage).
Step 7 Press [◄] key to return to the display of the Fn009.
Use the ESView V4
The following are the steps to execute the load inertia identification by using ESView V4.
Step 1 Select Advance → Load Inertia Identification in the Menu Bar of the ESView V4 main windows.