Summa Series Servodrive Product Manual
Basic Settings
Document Version: V1.01
(Dec, 2019)
© 2019 ESTUN Automation Co., Ltd. All right reserved.
4-4
Code
Meaning
Safe State
Forward Drive Prohibited
Reverse Drive Prohibited
(Forward and Reverse) Overtravel State
Alarm Number Display
NOTE: When the Drive is in Servo Alarm State, you shall check and correct the fault according to the Alarm Number
Display, and then, you can press [◄] key to try to clear the current alarm.
4.1.4 Parameter Setting Mode
Functions can be selected or adjusted by setting parameters. There are two types of parameters.
Function Parameters: the functions allocated to each digit of the Panel Operator can be selected.
Adjustment Parameters: a parameter is set to a value within the specified range of the parameter.
For a description of the parameter settings, please refer to the section 12.1 Parameters Lists.
Function Parameters Setting
The example below shows how to change parameter Pn003 (Application Function Selections 3) from
0000 to 1032.
Step 1 Press [M] key several times to select the Parameter Setting Mode.
Step 2 Press [▲] key or [▼] key to select the parameter Pn003.
Step 3 Press [◄] key to display the current value of Pn003.
Step 4 Press and hold [◄] key for 1 second or more, and then a flashing decimal point will appear at the bottom
right of the 5th digit.
Decimal point is flashing