EasyManua.ls Logo

Fike FCP-300 - Page 47

Fike FCP-300
175 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Notification Appliance/Auxiliary Power Circuits Control Panel Installation
FCP-300/FCP-300ECS Manual — P/N LS10145-002FK-E:A 3/12/2021 47
Figure 4.41 Class B Notification Appliance Circuit Wiring
The maximum voltage drop is 3V per Class A circuit. See Table 4.5.
Class A Notification Wiring
You must use an appliance from the list of compatible appliances in Appendix A.
To install a Class A notification appliance circuit, do the following.
1. Wire the Class A notification appliances as shown in Figure 4.42.
Current Maximum Impedance
1.0A 3Ω
1.5A 2Ω
2.0A 1.5Ω
2.5A 1.2Ω
3.0A 1.0Ω
Table 4.5 Maximum Impedance Class A
Alarm Polarity
4.7 kΩ EOL
Supervised
Power-Limited
Notification Wiring
Max. Impedance:
All Circuits are Synchronized
(Regulated). Rated at 27.4 VDC @ 3A
Max.
!
CAUTION:
For proper System supervision, do not use the looped wire under the terminals marked + and – of the Flexput connectors. The Break wire
runs to provide supervision of connections.

Table of Contents

Other manuals for Fike FCP-300

Related product manuals