3.4 Programming Mode
3-34
Table 3.4-12 “Maintenance Information” display items (cont.)
Monitor
No.
Symbol
Item
Displayed content
5_29
tM.M3
Cumulative run
time for motor 3
Displays the content of the cumulative power-ON time counter
of motor 3.
The display method is the same as for 5_23 above.
5_30
tM.M4
Cumulative run
time for motor 4
Displays the content of the cumulative power-ON time counter
of motor 4.
The display method is the same as for 5_23 above.
5_31
rt.M1
Remaining hours
before the next
maintenance 1
Displays the hours remaining before the next maintenance,
which is estimated by subtracting the cumulative run time of
motor 1 from the maintenance interval specified by H78. (This
function applies to motor 1 only.)
Display range: 0 to 99990
5_32
no.M2
Startup count for
motor 2
Displays the content of the motor 2 startup counter (i.e., the
number of run commands issued).
The display method is the same as for 5_08 above.
5_33
no.M3
Startup count for
motor 3
Displays the content of the motor 3 startup counter (i.e., the
number of run commands issued).
The display method is the same as for 5_08 above.
5_34
no.M4
Startup count for
motor 4
Displays the content of the motor 4 startup counter (i.e., the
number of run commands issued).
The display method is the same as for 5_08 above.
5_35
rno.M1
Remaining startup
times before the
next maintenance 1
Displays the number of startups remaining until the next
maintenance,
which is estimated by subtracting the number of startups from
the preset startup count for maintenance specified by H79.
(This function applies to motor 1 only.)
The display method is the same as for 5_08 above.
5_36
LALM1
Warning factor
(Latest)
Displays the factor of the latest warning as an alarm code.
For details, refer to Chapter 6 “6.1 Protective Functions.”
5_37
LALM2
Warning factor
(Last)
Displays the factor of the last warning as an alarm code.
For details, refer to Chapter 6 “6.1 Protective Functions”.
5_38
LALM3
Warning factor (2nd
last)
5_39
LALM4
Warning factor (3rd
last)
5_40
oPA.Er
Option A error
content
Displays the content of errors that have occurred in the option
installed in the A-Port.
5_41
oPb.nE
Number of option B
errors
Displays the total number of errors that have occurred in the
option installed in the B-Port.
Once the count exceeds 9999, the counter will be reset to “0.”
5_42
oPb.Er
Option B error
content
Displays the content of errors that have occurred in the option
installed in the B-Port.
5_43
oPC.nE
Number of option C
errors
Displays the total number of errors that have occurred in the
option installed in the C-Port.
Once the count exceeds 9999, the counter will be reset to “0.”
5_44
oPC.Er
Option C error
content
Displays the content of errors that have occurred in the option
installed in the C-Port.

Table of Contents