3.4 Programming Mode 
 
3-35 
OPERATION USING THE KEYPAD 
Table 3.4-12 “Maintenance Information” display items (cont.) 
Displays the type of option installed in the A-Port. 
See Table 3.4-13 for the display content. 
Displays the type of option installed in the B-Port. 
See Table 3.4-13 for the displayed content. 
Displays the type of option installed in the C-Port. 
See Table 3.4-13 for the displayed content. 
Maximum 
regenerative load 
factor value 
Displays the maximum value when the 5_51 inverter power 
is ON.   
The value returns to 0 when the inverter power is turned OFF. 
Displays the regenerative load factor in 100 s intervals. 
The value is calculated and updated every 100 s while the 
inverter power is ON. 
Maximum braking 
resistor operation 
frequency value 
Displays the maximum value when the 5_53 inverter power 
is ON.   
The value returns to 0 when the inverter power is turned OFF. 
Braking resistor 
operation frequency 
Displays the braking resistor operation frequency (time ratio) 
in 100 s intervals. 
The value is calculated and updated every 100 s while the 
inverter power is ON. 
Breaking resistor   
thermal overload 
relay operation 
value 
Displays the thermal overload relay operation value 
percentage at the current time. 
A dBH alarm occurs at 100%. 
Inverter thermal 
overload relay 
operation value 1 
Displays the thermal overload relay operation value 
percentage at the current time. 
An OLU alarm occurs at 100%. 
Inverter thermal 
overload relay 
operation value 2 
Displays the thermal overload relay operation value 
percentage at the current time. 
An OLU alarm occurs at 100%. 
Inverter thermal 
overload relay 
operation value 3 
Displays the thermal overload relay operation value 
percentage at the current time. 
An OLU alarm occurs at 100%. 
Estimates the IGBT life expectancy from changes in IGBT 
temperature, and displays the remaining times as a 
percentage. 
Can be displayed/output as warning iGb or LiF. 
A warning occurs if less than 10%. 
Display range: 0 to 100 %