5.2 Function Code Tables
Control method and Data setting range
0.00 to 6000 s
* 0.00 is for acceleration and deceleration time cancel (when
performing soft-start and stop externally)
-300 to 0 to 300%; 999 (Disable)
-300 to 0 to 300%; 999 (Disable)
Terminal [Y1]
(Function selection)
See E20 to E27 in “Table 5.2.3 Control output terminal setting list table”.
Terminal [Y5A/C]
(Ry output)
Terminal [30A/B/C] function
(Relay output)
Table 5.2.3 Control output terminal setting list table
Control method and Data setting range
Terminal [Y1]
to [Y4],
[Y5A/C],
[30A/B/C]
Terminal
[Y1A/B/C] to
[Y4A/B/C]
0 (1000): Inverter running
1 (1001): Frequency (speed) arrival “FAR”
2 (1002): Frequency (speed) detected “FDT”
3 (1003): Under voltage detected (inverter stopped) “LU”
4 (1004): Detected torque polarity “B/D”
5 (1005): Inverter output limiting “IOL”
6 (1006): Auto-restarting after momentary power failure “IPF”
7 (1007): Motor overload early warning “OL”
8 (1008): Keypad operation “KP”
10 (1010): Inverter ready to run “RDY”
11: Commercial/inverter power supply switching “SW88”
12: Commercial/inverter power supply switching “SW52-2”
13: Commercial/inverter power supply switching “SW52-1”
15 (1015): Switch MC on the input power lines “AX”
16 (1016): Pattern operation stage transition “TU”
17 (1017): Pattern operation cycle completed “TO”
18 (1018): Pattern operation stage 1 “STG1”
19 (1019): Pattern operation stage 2 “STG2”
20 (1020): Pattern operation stage 4 “STG4”
21 (1021): Frequency (speed) arrival 2 “FAR2”
22 (1022): Inverter output limiting with delay “IOL2”
25 (1025): Cooling fan in operation “FAN”
26 (1026): Auto-resetting “TRY”
27 (1027): Universal DO “U-DO”
28 (1028): Heat sink overheat early warning “OH”
29 (1029): Master-follower operation complete “SY”