EasyManua.ls Logo

Fuji Electric FRENIC MEGA G2 Series - Page 195

Fuji Electric FRENIC MEGA G2 Series
970 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.2 Function Code Tables
5-11
FUNCTION CODES
Chap 5
Function
code
Name
Control method and Data setting range
Change when
running
Data copying
Factory
default
Related page
E10
Acceleration time 2
0.00 to 6000 s
* 0.00 is for acceleration and deceleration time cancel (when
performing soft-start and stop externally)
Y
Y
*1
5-159
E11
Deceleration time 2
Y
Y
*1
E12
Acceleration time 3
Y
Y
*1
E13
Deceleration time 3
Y
Y
*1
E14
Acceleration time 4
Y
Y
*1
E15
Deceleration time 4
Y
Y
*1
E16
Torque limiter 2-1
-300 to 0 to 300%; 999 (Disable)
Y
Y
999
5-159
E17
Torque limiter 2-2
-300 to 0 to 300%; 999 (Disable)
Y
Y
999
E20
Terminal [Y1]
(Function selection)
See E20 to E27 in “Table 5.2.3 Control output terminal setting list table”.
N
Y
0
5-159
E21
Terminal [Y2]
N
Y
1
E22
Terminal [Y3]
N
Y
2
E23
Terminal [Y4]
N
Y
7
E24
Terminal [Y5A/C]
(Ry output)
N
Y
15
E27
Terminal [30A/B/C] function
(Relay output)
N
Y
99
Table 5.2.3 Control output terminal setting list table
Function code and name
Control method and Data setting range
E20 to E27
E71
o23 to o26
o121 to o128
Terminal [Y1]
to [Y4],
[Y5A/C],
[30A/B/C]
Keypad M-
LED indicator
Terminal
[Y1A/B/C] to
[Y4A/B/C]
Terminal [O1]
to [O8]
Y
Y
Y
Y
0 (1000): Inverter running
Y
Y
Y
Y
1 (1001): Frequency (speed) arrival “FAR”
Y
Y
Y
Y
2 (1002): Frequency (speed) detected “FDT”
Y
Y
Y
Y
3 (1003): Under voltage detected (inverter stopped) “LU”
Y
Y
Y
Y
4 (1004): Detected torque polarity “B/D”
Y
Y
Y
Y
5 (1005): Inverter output limiting “IOL”
Y
Y
Y
Y
6 (1006): Auto-restarting after momentary power failure “IPF”
Y
Y
Y
Y
7 (1007): Motor overload early warning “OL”
Y
Y
Y
Y
8 (1008): Keypad operation “KP”
Y
Y
Y
Y
10 (1010): Inverter ready to run RDY”
Y
N
Y
Y
11: Commercial/inverter power supply switching “SW88”
12: Commercial/inverter power supply switching “SW52-2”
13: Commercial/inverter power supply switching “SW52-1”
Y
N
Y
Y
15 (1015): Switch MC on the input power lines “AX”
Y
Y
Y
Y
16 (1016): Pattern operation stage transition “TU”
17 (1017): Pattern operation cycle completed “TO”
18 (1018): Pattern operation stage 1 “STG1”
19 (1019): Pattern operation stage 2 “STG2”
20 (1020): Pattern operation stage 4 “STG4”
Y
Y
Y
Y
21 (1021): Frequency (speed) arrival 2 “FAR2”
Y
Y
Y
Y
22 (1022): Inverter output limiting with delay “IOL2”
Y
Y
Y
Y
25 (1025): Cooling fan in operation “FAN”
Y
Y
Y
Y
26 (1026): Auto-resetting “TRY”
Y
N
Y
Y
27 (1027): Universal DO “U-DO”
Y
Y
Y
Y
28 (1028): Heat sink overheat early warning “OH”
Y
Y
Y
Y
29 (1029): Master-follower operation complete “SY”

Table of Contents

Related product manuals